| model | SB DT04 |
| order number | UN 288-5DT04-0AA0 |
| conventional | |
| Dimensions W x H x D (mm) | 35 x 52.2 x 16 |
| weight | 18.1 g |
| power consumption | 1.0W |
| Current Consumption (SM Bus) | 50 mA |
| Current consumption (24 V DC) | 4 mA per point input used |
| digital input | |
| Enter points | 2 |
| type | Sink (IEC Type 1 Sink) |
| Rated voltage | 24 V DC at 4 mA, nominal |
| Allowable continuous voltage | 30 V DC max. |
| surge voltage | 35 V DC for 0.5 s |
| Logic 1 signal (minimum) | 15V DC at 2.5mA |
| Logic 0 signal (maximum) | 5V DC at 1mA |
| Isolation (field side and logic side) | 500 V AC for 1 min |
| isolation group | 1 |
| filter time |
0.2, 0.4, 0.8, 1.6, 3.2, 6.4 and 12.8 µs individually selectable per channel 0.2, 0.4, 0.8, 1.6, 3.2, 6.4 and 12.8 ms |
| Simultaneously connected inputs | 2 |
| cable length | 500 m (shielded), 300 m (unshielded) |
| digital output | |
| output points | 2 |
| output type | Solid State - MOSFET (Source) |
| voltage range | 20.4 ~ 28.8 V DC |
| Logic 1 signal at maximum current | 20 V DC minimum |
| Logic 0 signal at maximum current | 0.1 V DC max. |
| Rated current per point (maximum) | 0.5 A |
| lamp load | 5W |
| On-state contact resistance | 0.6Ω max. |
| Leakage current per point | 10 μA max |
| Inrush current | 5 A for a maximum duration of 100 ms |
| overload protection | none |
| Isolation (field side and logic side) | 500 V AC for 1 min |
| isolation group | 1 |
| current per common | 1 A |
| Inductor Clamp Voltage | L + - 48 V, 1 W loss |
| switch delay |
Off-to-on max. 2 μs On-off max. 10 μs |
| Output status in STOP mode | previous value or replacement value (default is 0) |
| Simultaneously connected outputs | 2 |
| Cable length (maximum) | 500 m (shielded), 150 m (unshielded) |